Which functions can the local smart screen of the micro-module provide?
Select All that Apply.
Answer : B, C, D
Exact Extract --- Huawei HCSA-Presales-Data Center Facility (Modular DC) V1.0 Training Material,
PDF page 47
''Smart O & M: facial recognition for login and doors opening Liveness detection, Reliable effectively preventing video or photo unlock Facial recognition# * Logging in to the Management System through facial recognition in the local PAD * Opening the cabinet door Key data comparison: Accurate identification Fast recognition and wide range Efficient after wearing glasses, * Recognition time < 1s identification time < * Maximum identification distance: 3 m 1s * Accuracy #99.6% Facial data and operation recording * Supports facial data management of a Security algorithm, maximum of 16 authorized persons. Accurate facial recognition Traditional mode: mechanical key: * Operation data can be recorded to ensure accuracy > 99.6% Poor convenience security. 47''
Technical Deep Dive
The local smart screen provides visibility into core subsystem information and can display PUE. It also supports facial-recognition-based, keyless door opening, which is an access-control function. Facial recognition for local application login does not establish facial-recognition login for a surveillance system.
The local PAD displays subsystem information and supports operational functions such as a module PUE view. On appropriately equipped systems, facial recognition can authorize door opening. The training explicitly describes facial recognition for login to the local management application, not to the video surveillance system. These distinct login targets explain why the surveillance-system option is not supported by the cited wording.
Huawei's modular data center design emphasizes reliable power, controlled cooling, infrastructure monitoring and standardized deployment. The stated feature must be interpreted in its correct solution and configuration context. A compliant presales design combines equipment capacity, availability objectives, environmental conditions, physical installation requirements and the customer's operating needs.
Verification principle: confirm the exact product revision, operating condition, selected option and relevant Huawei documentation before using this result in a customer proposal. A feature shown for a particular configuration should not automatically be assumed to apply to every module or installation; normal technical, commercial and safety checks still apply.
Source reference: uploaded Huawei training material, PDF page 47.
In FusionModule800, what gas type does the fire-suppression module use?
Answer : B
Exact Extract --- Huawei HCSA-Presales-Data Center Facility (Modular DC) V1.0 Training Material,
PDF page 48
''Auto door: emergency heat dissipation and linkage with fire extinguishing High internal temperature Smoke alarm Fire Emergency Extinguishing heat dissipation linkage Cooling interruption Equipment room fire Power interrupted, Temperature sensor The controller Temperature rises Smoke sensor battery discharge alarm sends an alarm to alarm the building Fire gas released Doors open Extinguish the Doors are opened, and Hot air is expelled automatically. fire gas enters. 48''
Technical Deep Dive
The FusionModule800 fire-extinguishing module uses perfluorohexanone, a clean-agent suppressant also known as NOVEC 1230. Huawei's datasheet specifies a 6.25 kg perfluorohexanone agent capacity.
The supported extinguishing agent is perfluorohexanone, chemically FK-5-1-12 and associated with the Novec 1230 trade name. FM-200 refers to a different fluorinated agent, HFC-227ea; carbon dioxide is another distinct suppression gas with serious occupied-space hazards. The training confirms linkage between fire detection and extinguisher actuation, while the agent selection is confirmed by the relevant FusionModule800 equipment specification.
FusionModule800 uses standardized configurations for different power and availability needs. Engineers must distinguish UPS apparent-power rating, permitted IT load, cooling output, power-path redundancy and installed optional functions. Validating these parameters together prevents an apparently attractive cabinet combination from failing installation, thermal management or service-continuity requirements.
Verification principle: confirm the exact product revision, operating condition, selected option and relevant Huawei documentation before using this result in a customer proposal. A feature shown for a particular configuration should not automatically be assumed to apply to every module or installation; normal technical, commercial and safety checks still apply.
Source reference: uploaded Huawei training material, PDF page 48.
An in-row air-cooling unit is used in the FusionDC1000A-40ft-IT solution.
Answer : A
Exact Extract --- Huawei HCSA-Presales-Data Center Facility (Modular DC) V1.0 Training Material,
PDF page 58
''FusionDC1000A-40ft solution for IT Scenario 100% Prefabrication#Plug & Play Rack Power Cooling Fire protection Management 6/8*42U IT racks 2N & N+X available Air-cooled in-row Fire protection ECC800-pro (standard) 6-9kW / rack Modular UPS Hot aisle containment FK5112#standard# NetEco 6000 (Optional) Total IT power#54kW 12192mm2438mm2896mm Integrated Modular UPS In-row smart cooing Power Distribution + UPS save 1 UPS system efficiency up to 96% Wet-film Humidifier Save Energy ''0'' Condensation Risk@Low Load cabinet by 95% 58''
Technical Deep Dive
The FusionDC1000A-40ft-IT solution uses in-row precision air-conditioning units to provide cooling within the containerized IT deployment.
The data center uses air-cooled precision cooling units located in-row. The arrangement improves heat pickup close to the IT cabinets and uses containment to limit return-air mixing with supply air. Refrigerant equipment transfers heat outside the module, while electronic controls maintain environmental targets. This is functionally the same cooling concept assessed in Question 31, despite the alternative question wording.
For this prefabricated 40-foot product, presales validation must distinguish physical cabinet arrangements, IT power density, UPS architecture, environmental limits, in-row cooling and the enclosure rating. A statement for one configured version must not be generalized to every deployment. Final designs also require suitable foundations, upstream connections, local safety compliance and commissioning checks.
Verification principle: confirm the exact product revision, operating condition, selected option and relevant Huawei documentation before using this result in a customer proposal. A feature shown for a particular
configuration should not automatically be assumed to apply to every module or installation; normal technical, commercial and safety checks still apply.
Source reference: uploaded Huawei training material, PDF page 58.
Which of the following are features of the UPS2000-H in FusionModule800?
Select All that Apply.
Answer : A, B, C, D
Exact Extract --- Huawei HCSA-Presales-Data Center Facility (Modular DC) V1.0 Training Material,
PDF page 42
''Detailed introduction of basic configurations-1/2 Configuration BC1L BC2L BC3L BC4L BC5L Structure Single row, cold & hot aisle containment UPS(KVA) 10kVA 10kVA*2 10kVA*3 20kVA*2 20kVA*3 Air conditioner N, N+1 Power input Single input is default Qty of IT output 12 12 24 24 24 Qty of cooling output 3 2 3 3 6 Temperature sensor, smoke sensor, SMS alarm, local app on the mobile phone, PAD, intelligent door lock, ECC800 Standard (intelligent/ no-intelligent#RPDU, video system, power backup, IT rack, remote app on the mobile phone, network rack, water Optional sensor 42''
Technical Deep Dive
UPS2000-H provides an output power factor of 1, up to 96% efficiency in double-conversion mode, and an 80--280 V AC input-voltage range. When deployed in FusionModule800, it also supports the solution's remote monitoring and online maintenance and upgrade capabilities.
The applicable UPS2000-H specifications support an output power factor of one, high double-conversion efficiency up to 96 percent and a wide 80--280 V input range for the designated phase-voltage configuration. Remote monitoring can be provided through supported network cards and management software. The broad claim about remote online UPS upgrades depends on the specific device and firmware; management-card update functionality should not be confused with every form of UPS firmware upgrade.
FusionModule800 uses standardized configurations for different power and availability needs. Engineers must distinguish UPS apparent-power rating, permitted IT load, cooling output, power-path redundancy and installed optional functions. Validating these parameters together prevents an apparently attractive cabinet combination from failing installation, thermal management or service-continuity requirements.
Technical verification warning: Option C: online upgrades depend on model, firmware and installed management components.
Source reference: uploaded Huawei training material, PDF page 42.
Which of the following product information is available on the configuration result page?
Select All that Apply.
Answer : A, B, C, D
Exact Extract --- Huawei HCSA-Presales-Data Center Facility (Modular DC) V1.0 Training Material,
PDF page 94
''View Configuration Result On the Config Result tab page, you can obtain the detail information for the Spart, such as part number, model, list price, and quantity. Display range. Recommended value: Quantity > 0
+ Manual modification. By default, the Associated Calculation function is Click here, you can enabled. If associated select the columns calculation is disabled, to be displayed. modifying configuration You can select Show does not trigger real-time subitem in the upper right part calculation, and related of Config Result to view and configuration items are not export main equipment and automatically modified export subitems of a fixed or dynamic package. You can change the configuration result based on the site requirements. Different colors indicate different''
Technical Deep Dive
A configuration result page presents the configured product's description, product code, list price, and model information, allowing the user to identify the selected product and review its commercial details.
The configuration-result page displays sales-part identifiers, model, description, list price and quantity, with column selection and associated-calculation options. Descriptions aid human review, codes identify exact items, models distinguish variants and list prices support commercial calculations. These details help prevent part-number and quantity mismatches when finalizing a quote. The display can be adapted to project requirements.
In a production presales workflow, the configured BOQ must remain traceable to its customer and opportunity, and the product models, sales-part status, quantities and downstream commercial details must be validated before an order or quotation is finalized. A user-interface capability should not be mistaken for authorization to ignore an error or bypass role-based access restrictions.
Verification principle: confirm the exact product revision, operating condition, selected option and relevant Huawei documentation before using this result in a customer proposal. A feature shown for a particular configuration should not automatically be assumed to apply to every module or installation; normal technical, commercial and safety checks still apply.
Source reference: uploaded Huawei training material, PDF page 94.
In the FusionDC1000A-40ft N+X scenario, the UPS supports two ATS inputs and has a maximum power capacity of 60 kVA (with 2+0 redundancy).
Answer : B
Exact Extract --- Huawei HCSA-Presales-Data Center Facility (Modular DC) V1.0 Training Material,
PDF page 58
''FusionDC1000A-40ft solution for IT Scenario 100% Prefabrication#Plug & Play Rack Power Cooling Fire protection Management 6/8*42U IT racks 2N & N+X available Air-cooled in-row Fire protection ECC800-pro (standard) 6-9kW / rack Modular UPS Hot aisle containment FK5112#standard# NetEco 6000 (Optional) Total IT power#54kW 12192mm2438mm2896mm Integrated Modular UPS In-row smart cooing Power Distribution + UPS save 1 UPS system efficiency up to 96% Wet-film Humidifier Save Energy ''0'' Condensation Risk@Low Load cabinet by 95% 58''
Technical Deep Dive
For the FusionDC1000A-40ft IT N+X configuration, Huawei specifies two input channels and UPS capacity of up to 60 kVA, with 2+1 module redundancy. A 2+0 configuration has no module redundancy, so it does not describe the N+X configuration.
N+X and 2N describe different redundancy mechanisms. In the designated 40-foot N+X arrangement, a 2+1 modular UPS configuration means that an additional power module is available beyond the two required for capacity. A 2+0 arrangement has no spare module within that UPS and is associated with a different configuration. Confusing module redundancy with independent power-path redundancy can cause incorrect availability claims in customer proposals.
For this prefabricated 40-foot product, presales validation must distinguish physical cabinet arrangements, IT power density, UPS architecture, environmental limits, in-row cooling and the enclosure rating. A statement
for one configured version must not be generalized to every deployment. Final designs also require suitable foundations, upstream connections, local safety compliance and commissioning checks.
Source reference: uploaded Huawei training material, PDF page 58.
Which of the following door-opening methods are not used for the end doors of the FusionDC1000A prefabricated integrated data center?
Select All that Apply.
Answer : B, C
Exact Extract --- Huawei HCSA-Presales-Data Center Facility (Modular DC) V1.0 Training Material,
PDF page 58
''FusionDC1000A-40ft solution for IT Scenario 100% Prefabrication#Plug & Play Rack Power Cooling Fire protection Management 6/8*42U IT racks 2N & N+X available Air-cooled in-row Fire protection ECC800-pro (standard) 6-9kW / rack Modular UPS Hot aisle containment FK5112#standard# NetEco 6000 (Optional) Total IT power#54kW 12192mm2438mm2896mm Integrated Modular UPS In-row smart cooing Power Distribution + UPS save 1 UPS system efficiency up to 96% Wet-film Humidifier Save Energy ''0'' Condensation Risk@Low Load cabinet by 95% 58''
Technical Deep Dive
FusionDC1000A end doors are designed to open both inward and outward rather than in only one direction. Consequently, externally opening only and inward opening only are not used for those doors.
The designated main end entrance door can swing inward and outward. Consequently, inward-only and outward-only opening do not correctly describe that door. The original option about opening from inside and outside is semantically ambiguous because access from either side differs from swing direction. Huawei also distinguishes certain equipment and emergency doors, so the statement should identify the main end entrance specifically.
For this prefabricated 40-foot product, presales validation must distinguish physical cabinet arrangements, IT power density, UPS architecture, environmental limits, in-row cooling and the enclosure rating. A statement for one configured version must not be generalized to every deployment. Final designs also require suitable foundations, upstream connections, local safety compliance and commissioning checks.
Verification principle: confirm the exact product revision, operating condition, selected option and relevant Huawei documentation before using this result in a customer proposal. A feature shown for a particular
configuration should not automatically be assumed to apply to every module or installation; normal technical, commercial and safety checks still apply.
Technical verification warning: Original option wording conflates operating the door from a side and swinging in/out.
Source reference: uploaded Huawei training material, PDF page 58.